Every number on this site comes from a document I can point to:
Spotted a mistake, or have a document I should see? Write to daredavil239804@gmail.com with the page, the claim and, if you can, a source. I reply within 7 days and note every fix on the page.
How every number on this site is worked out: the evidence labels, the formulas and the 11 inputs behind them. Change an input and the whole site recalculates.
Documented official paper
Reported news or researcher
Alleged a named person says
Official claim developer or government
Every claim carries an evidence label:
The ⓘ beside a number opens the exact sentence it comes from, with the document and page. Numbers I computed are marked "derived" and show the formula.
Everything below is a model, not a measurement. Each input is listed with its source, and you can change any of them in model-params.json and rebuild.
For each Western Ghats project that has both a forest-land figure and a storage figure in its clearance papers:
forest ha per GWh = forest land (ha) ÷ storage (GWh)
14 projects have both. Together they need 1,331.2 ha of forest for 139.1 GWh of storage, an average of 9.6 ha per GWh. The range is wide: from 0 at Tarali, where the layout was revised off forest land, to 22.1 at Bhavali.
Pipeline extrapolation (illustrative). Maharashtra has signed MoUs for 78,215 MW of pumped storage. At an assumed 6 hours each, that is 469 GWh. At the average above, that would need about 4,500 ha of forest. This is an illustration of scale, not a forecast: many MoUs will never be built, and siting changes the answer a lot.
Limits.
A pumped storage plant pumps water uphill with grid power and releases it later. Some energy is lost each cycle. The share that comes back is the round-trip efficiency, η. I use η = 0.775, the 22.5% declared cycle loss in Tamil Nadu's 2026 tariff order, the best contractual figure in India.
energy in = energy out ÷ η loss = energy in − energy out
Daily full cycle. If the whole pipeline (469 GWh) filled and emptied once a day, it would lose 136 GWh a day, or 49.7 TWh a year.
At a realistic utilisation. Karjat's environmental clearance expects 6,241.5 million units a year from 3,000 MW, a capacity factor of 23.7%. Applied to the pipeline:
output = MW × 8,760 h × capacity factor loss = output × (1/η − 1)
That gives 162 TWh a year delivered and 47 TWh a year lost, about 2.7% of India's net generation in FY2025-26 (1,761.28 TWh).
Sensitivity. Typical plants range from 0.7 to 0.8:
| η | Lost per day, full cycle (GWh) | Lost per year at reference capacity factor (TWh) |
|---|---|---|
| 0.7 | 201 | 70 |
| 0.775 | 136 | 47 |
| 0.8 | 117 | 41 |
Limits. The pipeline will not all be built, and real plants do not cycle at a fixed rate. The loss is real only if the charging power would otherwise have been used; power that would have been curtailed is not a loss in practice.
Storage has no chimney, but it moves emissions in time. Whether it cuts or adds CO₂ depends on which power plants run more when it pumps and which run less when it generates. I use the Central Electricity Authority's CO₂ Baseline Database for FY2025-26: grid weighted average 0.675 t CO₂/MWh and operating margin (the plants that change output first, mostly coal) 0.963 t CO₂/MWh.
Two ways to count.
Attributional intensity: I = EF_charge ÷ η + LCA_infra
Consequential change: ΔCO₂ = EF_charge,marginal ÷ η − EF_displaced,marginal
Scenarios (t CO₂ per MWh delivered).
| Scenario | Charged by | Displaces | Result |
|---|---|---|---|
| (a) Coal margin | operating margin | operating margin | +0.28 |
| (a′) Grid average | weighted average | (attributional) | 0.87 before infrastructure |
| (b) Curtailed solar | solar that would be wasted | operating margin | -0.96; -0.88 with infrastructure |
In case (a), on 162 TWh a year, the pipeline would add about 45 million tonnes of CO₂ a year. This is an upper bound.
Infrastructure emissions use the NREL life-cycle study of closed-loop pumped storage, base case 86 g CO₂e/kWh (0.086 t/MWh). The study's range is 58–530.
Break-even. If a share s of charging is curtailed solar and the rest is coal margin:
ΔCO₂(s) = (1 − s) × EF_OM ÷ η − EF_OM
This is zero at s = 1 − η. So storage cuts emissions only when more than 22.5% of the charging energy is solar that would otherwise be wasted, or 29.4% once infrastructure is counted.
Limits. Real dispatch is hour by hour; a single margin factor is a simplification. As solar grows, case (b) becomes more common. Developer claims of avoided CO₂ implicitly assume all charging is zero-carbon.
Tariffs are quoted in different units (₹ lakh per MW per month, ₹ crore per MW per year) for plants with different durations. I put them on one basis: ₹ lakh per MWh of storage capacity per year.
₹ lakh/MWh/yr = (₹ lakh per MW per year) ÷ duration (h) (monthly tariffs × 12; ranges use the midpoint)
Recent Indian tenders give 8.6–14.3 for batteries (2–4 h) and 9.7–13.6 for pumped storage (8 h). Every tender used is listed with its source in model-params.json.
Limits. A tariff is a price, not a full cost: viability gap funding, contract length (40 years for SECI's pumped storage tender), degradation and the round-trip loss are not equalised. Batteries and pumped storage of different durations do different jobs.
src/lib/data/model.ts. Inputs: data/model-params.json. Output: data/generated/stats.json.78,215 MW
pipeline-mw
6 h
Assumption; most MoUs state ≥6 h.
assumed-duration-h
0.775 fraction
round-trip-efficiency
0.7 fraction
round-trip-efficiency-low
0.8 fraction
round-trip-efficiency-high
0.237 fraction
reference-capacity-factor
1,761.28 TWh
india-net-generation-twh
0.675 tCO2/MWh
grid-ef-weighted-average
0.963 tCO2/MWh
grid-ef-operating-margin
86 gCO2e/kWh
Range 58–530.
psh-lca-base-gco2-kwh
400 MW
maharashtra-operating-psp-mw